Solar Hot Water System Troubleshooting Table For Pressurized (PS) and Drainback Systems (DS) | |||
---|---|---|---|
Complaint |
Symptom |
Problem |
Action |
Insufficient heat (PS) |
Collector loop shows loss of pressure |
Collector loop airbound |
*Check for and repair leaks *Check Pressure Relief Valve *Check air vents if present *Refill and re-purge system |
(PS + DS) |
|
Leak in collector |
*Repair or replace absorber plate or vacuum
tube |
(DS) |
No fluid flow in solar loop |
High-head pump airbound |
Pump improperly located - relocate |
(DS) |
|
High-head Pump failure |
Replace pump |
(DS) |
|
High-head Pump undersized |
Upgrade pump |
(DS) |
|
Collector loop Piping sagging |
Check for sagging pipes, repair and add pipe
hangers (one every 4' min.) |
(DS+PS)) |
|
Pump OK but pump does not run |
See Systems not running at correct times |
(PS) |
Collector loop shows no loss of pressure |
Collectors not receiving energy or undersized |
*Check collectors
|
(PS) |
|
Collector loop airbound |
Repurge system |
(PS+DS) |
|
Circulator impeller Jammed |
*Strike sharply when power is applied to free
rotor *Replace pump cartridge or pump |
(PS + DS) |
|
Valves or pump isolation valves shut off |
Open valves |
(PS+DS) |
|
Bent or crushed pipes |
Repair/replace pipe |
(PS+DS) |
|
Individual tubes in
evacuated collector failure |
Inspect and replace
as needed |
(PS+DS) |
|
Obstruction on
collector loop |
*In the collector
array, unequal collector outlet temperature will show obstructed collector *Check heat exchanger *flush & refill |
(PS+DS) |
|
Potable water lines airbound |
*Check air vents in
potable water lines for proper location and operation *Check for air in potable
water side of heat exchanger |
(PS+DS) |
|
Heat exchanger,
Pump(s) or piping too small |
Check sizing charts
and correct |
(PS) |
|
Faulty or incorrectly
installed check valve |
*Confirm flow is in
correct direction *Check for correct
valve operation *Check for blockages |
(PS+DS) |
|
Tempering valve set
too low or not operating properly |
Reset or replace |
(PS) |
Large pressure
fluctuations in collector loop |
Air in loop |
*Check for leaks and
repair *Check pressure
relief valve and replace if necessary *Check air vents (if
any) and replace or isolate if necessary *Purge air from
system |
(PS) |
|
Expansion tank |
*Check expansion tank
for fluid in air chamber and replace if necessary *Make sure to set
expansion tank pressure to 25# before installing *Expansion tank too
small. Calculate proper size and replace if needed |
(PS+DS) |
Storage tank loosing
heat, especially at night |
Tank poorly insulated |
Insulate tank to R-10
or more if the tank is in a poorly insulated area |
(PS) |
|
Reverse
thermosiphoning |
Inspect check valve
and replace if needed |
(PS+DS) |
Piping loosing heat |
Improper or
insufficient insulation |
Repair or replace |
(PS+DS) |
Storage tank gets
hot quickly but also runs out of hot
water quickly |
Storage tank too
small |
Increase storage tank
size or add a second tank |
(PS+DS) |
Solar tank warm but
back-up water heater not warm |
Faulty back-up water
heater |
Repair or replace |
(PS+DS) |
System does not run
consistently |
Controller, sensor or
wiring problems |
See Systems not
running at correct times |
(PS+DS) |
Gradual performance
decrease |
Collector shaded |
Clear obstruction |
(PS+DS) |
|
Collector glazing
dirty |
Clean collectors |
(PS+DS) |
|
Excess condensation
inside collectors |
*Check collector
vents or weep holes and clean if needed *Check for a slow
leak inside collector and repair/replace as needed |
(PS+DS) |
|
Pipe insulation
degrading |
Replace as needed |
(PS+DS) |
|
Heat exchanger
clogged |
Check for proper
fluid flow through heat exchanger (both sides) and clean or replace as needed |
Systems not running
at correct times (PS+DS) |
Pump(s) running all
the time |
Controller switch in
"ON" position |
Move switch to "Auto"
position |
(PS+DS) |
|
Collector sensor or
leads shorted or storage leads broken (find with ohmmeter) |
Correct malfunction.
Replace sensor if needed |
(PS+DS) |
Pump(s) never running |
No power to
controller (AC powered) |
Restore power |
(PS+DS) |
|
Controller switch in
"off" position |
Move switch to "Auto"
position |
(PS+DS) |
|
Storage sensor leads shorted
or collector sensor leads broken (find with ohmmeter) |
Correct situation.
Replace sensor if needed |
(PS+DS) |
Pump(s) running at
intermittent times |
Corroded or loose
sensor wire connections |
Clean wire
connections of corrosion and re-connect with watertight connectors or solder
connections. Never use wire nuts on sensor wiring. |
(PS+DS) |
|
Sensor leads run near
110 VAC wiring |
Move sensor wire at
least 6" away from 110 VAC wiring or use coaxial cable |
(PS+DS) |
|
Sensors incorrectly
placed, poorly secured or improperly insulated |
Move sensors to
correct location and properly insulate |
(PS+DS) |
|
Sensors improperly
wired |
Rewire following
instructions supplied with the controller |
(PS+DS) |
Any of the above |
Faulty controller |
Check controller and
replace as needed |
(PS) |
PV powered systems |
Loose wiring
connections |
Rewire |
(PS) |
|
PV panel undersized |
*Check wire size
chart for proper wire size and replace wire as needed *Replace PV panel
with proper size |
There are a host
of good reference materials available, some of which are listed here. Thanks to Kari Heinrich for providing this table, which was produced for the Focus on Energy solar hot water conference in the Wisconsin Dells, Dec. 2007. |